ICS TRIPLEX T8403C 40‑Channel TMR Digital Input Module (SIS)
- Product Code: T8403C
- Availability: In Stock
Purchase Attributes:Original, Brand New
Service Attributes
▷ Stock & Logistics:Fast Delivery
▷ After-sales Guarantee:12 Months Warranty
▷ Online Customer Service:24 Hours Online Support
▷ Product Advantages:Competitive Price, Long Service Life
Application Attributes:ICS TRIPLEX T8403C 40‑Channel TMR Digital Input Module (SIS)
ICS TRIPLEX T8403C Trusted TMR Digital Input Module
Manufacturer: ICS TRIPLEX (Rockwell Automation)
Model: T8403C
Type: 40‑Channel TMR Digital Input Module (SIS)
Certification: SIL 3 (IEC 61508), TÜV Rheinland, Cat 4 / PLe
1. Overview
The ICS TRIPLEX T8403C is a high‑integrity TMR digital input module for the Trusted® safety system. It offers 40 triple‑redundant channels for 24 VDC discrete signals (dry/wet contact compatible), with per‑channel line monitoring (open/short circuit). It provides 1 ms SOE resolution, 1500 V isolation, and hot‑swap capability for safety‑critical SIS applications in oil/gas, chemical, and power industries.
2. Technical Specifications
• Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
• Channels: 40 digital inputs (triple redundant per channel)
• Input Voltage: 18–32 VDC (24 VDC nominal)
• Signal Type: Dry contact / NPN/PNP sensor (24 VDC)
• Isolation: 1500 V (channel‑to‑backplane)
• SOE Resolution: 1 ms (on‑board sequence of events)
• Line Monitoring: Per‑channel open/short circuit detection
• Scan Time: 1.174 ms / 2.202 ms (dual‑scan optional)
• Power: 10 W max, 24 VDC from backplane
• Temperature: −40 °C to +70 °C (operating)
• Dimensions (W×H×D): 302 × 265 × 30 mm; Weight: ~1.2 kg
3. Key Features
• SIL 3 TMR Safety: 2oo3 voting, single‑fault tolerant
• 40‑Channel High Density: 40 TMR inputs in compact size
• Per‑Channel Diagnostics: Open/short circuit detection
• 1 ms SOE: Precise event timestamping for root‑cause analysis
• Hot‑Swap: Online replacement without system shutdown
• Wide Temperature: −40 °C to +70 °C for harsh environments
4. Applications
• Oil & Gas: ESD, valve position, pressure/temperature switches
• Chemical: Reactor interlocks, emergency stop, fire/gas detection
• Power: BMS, turbine trip, generator protection, grid interlocks
• Process: Pharmaceutical, pulp & paper, water treatment safety I/O
ICS TRIPLEX © T8403C Trusted TMR Digital Input Module